Description
UT595 is a multifunction digital safety testing instrument, designed with combination of large-scale integrated analog & digital circuits and micro-processor chip. It mainly measures RCD, line/loop impedance, continuity, insulation resistance, DC and AC voltage, phase sequence, featuring versatile functionality, higher accuracy, stable performance and ease of use. The instrument is widely used to measure RCD, insulation and earth connections for various equipment, and an ideal tool for testing, inspection and maintenance badly needed for various electric devices and RCDs.
1. 9999-count LCD display with analogue bar
2. 250V~1000V DC insulation resistance test
3. 200mA earth-resistance continuity test
4. Loop impedance/Prospective Fault Current (PFC)/Prospective Short Current (PSC) test
5. Lock test
6. RCD trip time test and the data storage with one key
7. Full/Half wave and count downing (30s) test mode selectable
8. 0°/180° phase angle option to detect the fastest trigger time
9. Trip current test of RCD trip time X2
10. RCD trip trigger current test
11. Phase sequence and missing test
12. AC/DC voltage auto check and test
13. Connection check with status real-time display
14. White backlight; auto power off
Specifications | Range | Best Accuracy | |
Model | UT595 | ||
Insulation resistance (Ω) | Output voltage | 250V/500V/1000V | ±10% |
250V | 0.05MΩ~250MΩ | ±(5%+5) | |
500V | 0.05MΩ~500MΩ | ||
1000V | 0.05MΩ~1000MΩ | ||
Short-circuit current | <2mA | ||
Low-resistance continuity test | Range | 0.00Ω~199Ω | ±(2%+5) |
Test current | 0.00~2Ω: >200mA | √ | |
Line impedance (Ω) | Range | 0.01Ω~2000Ω | ±(5%+5) |
Operating voltage (Frequency) | 195V~440V (45Hz~65Hz) | √ | |
Test current | 20A | √ | |
PFC test | 0kA~26kA | √ | |
Loop impedance (Ω) | Range | 0.01Ω~2000Ω | ±(5%+5) |
Operating voltage (Frequency) | 195V~253V (45Hz~65Hz) | √ | |
Test current | 20A | √ | |
PFC test | 0kA~26kA | √ | |
Non-trip loop impedance (Ω) | Range | 1.00Ω~2000Ω | ±(5%+5) |
Operating voltage (Frequency) | 195V~253V (45Hz~65Hz) | √ | |
Test current | 15mA | √ | |
PFC test | 0kA~26kA | √ | |
RCD test | Operating voltage (Frequency) | 195V~253V (45Hz~65Hz) | √ |
Test current | 10mA/30mA/100mA/300mA/500mA | ±10% | |
Trip time | ×1/2 *I△n Range: 0ms~2000ms | ±(5%+5) | |
×1 *I△n Range: 0ms~300ms | |||
×1 *I△n Range: 0ms~500ms (Select count down) | |||
×2 *I△n Range: 0ms~150ms | ±(5%+5) | ||
×2 *I△n Range: 0ms~200ms (Select count down) | ±(5%+5) | ||
×5 *I△n Range: 0ms~40ms | ±(5%+5) | ||
Phase sequence test | Operating voltage (Frequency) | 100V~440V (45Hz~65Hz) | √ |
Display | Phase sequence: L1→ L2→ L3, forward rotation; L1→ L3→ L2 reverse rotation | √ | |
Ramp RCD test | Test current | 10mA/30mA/100mA/300mA/500mA | ±10% |
AC voltage (V) | Range | 0V~440V | ±(5%+2) |
Frequency response | 45Hz~60Hz | √ | |
Resolution | 1V | √ | |
Features | |||
Display count | 9999 | ||
Auto power off | √ | ||
Low battery indication | √ | ||
Data storage | √ | ||
LCD backlight | √ | ||
Auto half-wave test | √ | ||
RCD count down test | 30s | √ | |
RCD half-wave test | √ | ||
Phase conversion (RCD) | 0° and 180° | √ | |
General Characteristics | |||
Power | 1.5V battery (5#) × 6 | ||
LCD size | 125mm × 37mm | ||
Product color | Red and grey | ||
Product net weight | 1000g | ||
Product size | 210mm × 175mm × 90 mm | ||
Standard accessories | Battery, test leads (red×1, green×1, black×1), special power test lead, remote-control test lead |
UNI-T UT595 Multi-Function Installation Tester in Pakistan